Configuring the Scan Input Table

The following table outlines the device-dependent information that you must supply in the scan input table attribute for the DNPScanner:

  Field Number Field Name DE Type Possible Values
Device Independent 0 point control rtLOGICAL 0=disabled, 1=enabled
1 point status rtUINT8 §To configure the scan input table
2 poll type mask rtBYTES4 32-bit mask
3 st buffer size rtUINT16 0
4 SSMA offset rtUINT32 12 to 4,294,967,295
5 # of elements rtUINT16 1 to 65,535
6 RTAP DE type rtUINT8 1 to 31
7 deadband type rtUINT8 §To configure the scan input table
8 deadband rtDOUBLE any double
9 link address rtDB_XREF  
10 reserved1 rtINT32  
Device Dependent (DNP 3.0 scan task specific) 11 function code rtUINT8 (see below)
12 object group rtUINT8 (see below)
13 object variation rtUINT8 (see below)
14 qualifier rtUINT8 (see below)
15 range start rtUINT32 (see below)
16 range length rtUINT32 (see below)
17 data rtDB_XREF (see below)
18 bit rtINT8 (see below)
19 count rtUINT8 (see below)
20 unsolicited rtUINT8 (see below)
21 class number rtUINT8 1 to 3
22 reserved2 rtUINT32  
Optional .      
.      
.      

See also: