Fields to Configure in the Scan Input Table

Field Name Description
base The base name of signal name.
extension The extension name of the signal name.
attribute The attribute name of the signal name.
object type

This field is used when reading array data and can have the following values:

Value Description
0 Analog array object
1 Logical array object
field selector

This field allows for selecting various data to be returned and can have the following values:

Bit Numbers Description
7 (MS) Type and inhibit type
6 Value
5 Units/Logical Text
4 MSD Address
3 Name Text
2 Alarm Status
1 Descriptor Text
0 (LS) Logical ON/OFF Text
array/list #

This field is used it indicate which list number to read when reading a list, or the data array number when reading an array.

[warning] This field must be set to zero for non-array data.
start This field is used when reading list data, array data, raw I/O data or memory data. When reading list data, this field specifies the starting list element (usually zero). When reading array data, this field specifies the starting row in the array (counting from one). When reading raw I/O data, this field specifies a 16-bit I/O address. When reading memory address, this field specifies the starting 16-bit segment address.
end This field is used when reading list data, array data, raw I/O data or memory data. When reading list data, this field specifies the last element (must be greater than "start"). When reading array data, this field specifies the starting column in the array (counting from one; and is usually one). When reading raw I/O data, this field specifies a 16-bit I/O address. When reading memory address, this field specifies the second part of the starting 16-bit segment address.
msd This is the Master Signal Directory number for the given signal name. This value is retrieved from the RTU when the optimize attribute is set and whenever there is a version number mismatch.